Request a quote
Benešl Automation / BALANS / Manuals / BALANS POWER Heat / BALANS POWER Heat Triac
Installation and user manual · code 03I-T

BALANS POWER Heat Triac

Two 230 V thermal actuators and two temperature sensors for underfloor heating.

Status: in development board rev A0 manual version 1.2 (draft), 12. 11. 2026 firmware 2.38.3

BALANS POWER Heat Triac

1What the module is for

The module switches two 230 V thermoelectric valve actuators (triacs, zero-crossing switching) and measures two temperatures, typically the floor in two zones. The heating demand comes from the switch thermostat, Home Assistant, the scheduler or a button. The module's protection layer decides about the valve.

The variant with a 16 A relay and consumption metering is a separate module POWER Heat Relay.

Every BALANS switch consists of three layers in a single Kopos box KPR 68-70_KA (depth 70 mm): the front panel FACE behind glass, the control board CORE and the power module POWER at the bottom of the box. The boards are held by a printed carrier screwed into the lugs of the box. The panel and the 84 × 84 mm glass sit in a frame that snaps onto the carrier.

  wall <-------------------------------------------------> room
   POWER module | carrier | CORE | air | FACE panel | glass | frame
        +-- header 2x5 --+          +---- FFC 24p (type B) ---+
BALANS POWER Heat Triac board – top view
BALANS POWER Heat Triac board – top view

2Safety

  • The circuit must be protected by an upstream circuit breaker (max. B10, preliminary) and a 30 mA residual current device where required by ČSN 33 2000-4-41 (HD 60364-4-41).
  • The fuse in the module protects only the internal power supply. The loads are protected only by the upstream circuit breaker.
  • With mains connected, do not plug in the USB-C of the CORE control board and do not remove the front of the switch (frame with panel and glass). The service frame with the USB opening must not be used with 230 V modules.
  • The product is only for dry indoor rooms (IP20). Do not use in bathroom zones 0–2 or outdoors.
  • Run SELV conductors (low voltage, Ethernet, RS485, sensors) in the wall box separately from the 230 V conductors, with insulation rated for the highest voltage in the box.
  • After installation, carry out the inspection and testing per ČSN 33 2000-6 (HD 60364-6) where required.

3Terminals and wiring

TerminalMarking on the boardConnect
J2 (5.08 mm)Lphase from the circuit breaker
J2Nneutral
J3 (5.08 mm)OUT1thermal actuator 1
J3NN of the actuators (middle)
J3OUT2thermal actuator 2
J4 (3.5 mm)S1temperature sensor 1
J4S2temperature sensor 2
J4GNDcommon sensor wire
 breaker --> J2:L, J2:N
 J3:OUT1 --> actuator 1 --> J3:N <-- actuator 2 <-- J3:OUT2
 J4:S1 --[sensor 1]--+
 J4:S2 --[sensor 2]--+--> J4:GND
  • Connect only thermal actuators (resistive load) to the outputs. No lights or motors (for lights use POWER Triac).
Board with terminals and connectors. The terminal labels are on the board silkscreen (see the top view)
Board with terminals and connectors. The terminal labels are on the board silkscreen (see the top view)

4Mounting

  1. Switch off the circuit breaker (disconnect power) and verify that it is de-energised.
  2. Wire the terminal plugs off the board. The terminals are pluggable: wire the screw plug on the bench according to the terminal table and the markings on the board, then push it onto the pin header on the module.
  3. Screw the module from behind into the carrier posts (2× screw for plastic 3 × 6). The 2×5 header faces the carrier.
  4. Run the wires from below along the box wall and into the plugs from the side facing the centre of the board (the terminals face the centre; at the board edge the box wall blocks access).
  5. Screw the carrier into the box lugs (2× M3 countersunk), arrow pointing up.
  6. Fit the CORE control board onto the 2×5 header (pins straight, not offset by a row) and screw it down (2× screw 3 × 6).
  7. Assemble the front on the bench: stick 4 foam pads 1 mm onto the frame posts, place the panel on the 4 pins (M2.5 holes in the corners), put on the 84 × 84 × 2 mm glass and push it under the 4 spring clips. On a frame with glued-in glass, the glass is glued onto the frame shoulder.
  8. Connect the checked FFC cable type B to the panel and to the CORE board (lock the levers) and snap the whole front onto the carrier.

5Technical data

ItemValue
power supply230 V~ 50 Hz, N required
outputs2 × 230 V triac, zero-crossing switching, max. 0.5 A per channel (actuators typically draw 1–3 W)
temperature inputs2 × PT1000 or NTC (presets 10k, 11.5k, 12k, 100k or custom R25 1–200 kΩ and B), 16-bit converter
protectionfuse F1 T2A only for the internal power supply, varistor at the input
terminalsJ2 and J3 pluggable 5.08 mm; J4 pluggable 3.5 mm, 3 pins
networkWi-Fi
board revisionA0

Load ratings are preliminary until heating tests are complete.

Suitable and unsuitable loads

SuitableUnsuitable
230 V thermoelectric actuators, preferably NC (normally closed)lights, motors, heating cables and heaters (use POWER Heat Relay for these)

6Commissioning

  1. Switch on the circuit breaker (or connect PoE / power). The front panel lights up.
  2. Without Ethernet and without a configured Wi-Fi, the switch starts its own setup Wi-Fi “SmartButton-XXXX” (XXXX = end of the MAC address). The password is the 8-digit setup code from the label. The administrator can find it later in the web interface too (card “About the device and support”, button “Show code”, confirmed with the password). On the FACE Display panel the code appears on the display in the settings window (hold the centre for 5 s).
  3. Connect a phone or laptop and open http://192.168.4.1.
  4. Set the web password (8–31 characters) and give it to the user together with the label.
  5. The web interface offers the Setup wizard: name and room, front panel and power module (the wizard shows which module the switch has detected), touch calibration, Wi-Fi and time zone, Home Assistant (MQTT), default button layout and a summary. Nothing is written to the switch before the last step. After a change of panel or module the switch restarts and the wizard continues.
  6. No output moves until a module is selected. If the selected module does not match the connected one, the outputs stay off and the web interface shows the reason (code E02). A new switch can also select the module by itself: after the first power-on nothing happens, after the second the module is set (POWER Relay and Triac with mains connected, RGBW with the newer board, Base from PoE, PoE IO). The outputs then stay off until someone switches them on for the first time. Heating, blinds and modules in development are not set automatically. If the switch is to stay without a module, confirm “No module” on the Hardware page.
  7. Test all outputs and touch areas.
  8. The web interface is then at http://<name>.local or at the IP address from the router. With Ethernet (POWER Base, POWER PoE IO) the switch gets its address from DHCP.

Touch calibration is done through the glass once the front is assembled. It can be started in three ways: in the wizard (step Touch), on the Touch page with the “Calibrate on device” button (the LEDs under the areas guide you: white = do not touch, green = touch and hold, blue = release; at the end green = saved, red = weak area), or right on a new switch without a password: for the first 2 minutes after power-up the LED under the first area slowly “breathes” white, and holding this area alone for 3 s starts the calibration. The areas keep switching as usual meanwhile.

Calibration is also started by a short press of the BOOT button on the control board. On a panel with a slider, the slider finally lights up green: slide slowly along it from one end to the other. After power-on the switch does not respond to touch for about 3 seconds while it measures the idle values of the areas; lights that are to be on after power-on light up immediately.

If Wi-Fi does not connect, the web interface says why in plain words: the network was not found, the password does not match, or the security does not fit. It shows the signal strength with four bars and a word (excellent to very weak) in the header and on the Network page. A hidden network does not appear in the list; type its name by hand.

Web modes: Standard, Advanced and Expert (System → Web appearance). The mode only hides pages and cards an ordinary user does not need. The configured values remain, and warning cards are never hidden. The web interface is in Czech, Slovak, English, Polish and German and is adapted to phones as well. Explanations are short; details open with the “i” button.

Setup mode can be opened again with a gesture: hold two touch areas firmly at the same time for 5 s (FACE Display: the centre of the display for 5 s), or the BOOT button on the control board for 3–10 s. The setup Wi-Fi starts for 5 minutes and the LEDs flash blue. Without Ethernet it also starts when the switch cannot connect to the network for 3 minutes.

Time: the switch takes the time from the internet (NTP). In a network without internet it takes it from the browser after the administrator logs in. Without valid time the scheduler, the night mode and the weekly thermostat programme wait (code E12).

Home Assistant: turn on MQTT and “HA discovery” in the web interface; the entities appear by themselves and are placed in the given room. PLC: Modbus TCP is off by default and is enabled in the web interface (Integrations), preferably read-only and with an allowed IP address. The switch belongs in a separate network (VLAN). Remote access only through Home Assistant or a VPN, never by port forwarding.

Firmware is updated by a technician in the web interface (System → Updates) with a file supplied by the manufacturer. The update is signed. The new firmware is confirmed once the network and the web interface come up after the restart; otherwise the switch rolls back to the previous version by itself within 5 minutes. An update from an address needs a direct link; the switch rejects redirects. Optionally you can enable nightly automatic update from a private https address (off by default): it only runs at the chosen hour, when nothing is lit, no shutter is moving and nobody has touched the switch for 30 minutes. The firmware is not published. This manual describes firmware 2.38.3 (built and signed, not yet verified on the device).

Handover to the customer (System → Maintenance): one action for the installer at the end of the installation. It asks for the administrator password again, offers to set the password of the “control only” user and a new administrator password that only the customer will know (both can be skipped), then it deletes the traces of testing: event log, charts, consumption estimate, log, API tokens, webhooks and the syslog target, and ends all sessions. Optionally it also deletes the stored Wi-Fi. Installation settings, calibration, scenes, scheduler, integrations and passwords remain; the dialog lists which access credentials are left in the switch.

Settings change history (System): the last 8 saved changes with the time and the area they concerned, without values. The “Undo last change” button returns the settings to the state before the last change. Passwords, tokens, keys and the hardware selection are not reverted.

Factory reset from the web interface requires the administrator password to be entered again. With the BOOT button on the board (hold for 10 s) it works without a password; holding it for a shorter time does not reset the switch.

Device health (Diagnostics page): in one word “OK”, “Warning” or “Error”, and below it why and what to do about it. The administrator also finds a list of the last 8 firmware crashes there; if crashes repeat, send it to the manufacturer. The same status is in Home Assistant.

Manuals: the “About the device and support” card has links to the manual for the panel, the module and the control board at benesl-automation.cz/balans/navody/.

Service: System → Maintenance → Service bundle saves one file with the version, status, diagnostics and settings without passwords and keys. It contains network names and IP addresses, so send it only to the manufacturer, not publicly.

7LEDs and module settings

LEDMeaning
green (very dim)module has 5 V power

Settings according to the driver in the firmware (page Outputs): for each zone the sensor type, the actuator type (NC / NO) and the limits. The card with the limits and the warning is not hidden in the web interface in any mode.

Sensor type is selected in the web interface for each input: PT1000, or NTC with the preset 10k (default, B 3950), 11.5k, 12k, 100k or custom R25 and B values. The web interface shows the live sensor resistance and can calculate B and R25 from two measured points; the correction is ±5 K. For the 11.5k, 12k and 100k presets the B constant is not verified (the web interface marks them “B not verified”): with B off by 10 % the error is about 0.2 K at 27 °C and up to 1.6 K at 40 °C. Raychem 12k sensor: select the 12k preset and verify it by entering two points or with a reference thermometer. Invalid sensor settings are treated as a sensor fault and the zone does not heat (code E24).

Protection (in order of priority)DefaultRangeWhat it does
sensor fault––the zone does not heat (open circuit, short circuit, implausible value)
hard limit40 °C25–60 °Cno zone heats when any sensor exceeds the limit
floor limit27 °C15–35 °Cthe zone does not heat until the temperature drops by 1 K
frost protection5 °C0–12 °Cheats even without demand, unless the protections above prevent it

Regulate by (Advanced mode): room (default) or floor. In floor mode the thermostat setpoint is taken as the floor temperature and is limited so that it stays below the floor limit (with a 27 °C limit at most about 25.7 °C, at least 10 °C). A room sensor is then not needed and the open-window pause is off. The floor limit and the hard limit still switch off independently. If the floor sensor fails, the module does not heat (codes E24 and E09); frost protection then heats only by the room sensor, and not at all without it. The regulated temperature and the setpoint in use are shown in the web interface, Home Assistant, Modbus (IR 97 to 99) and the Thermostat widget on the FACE Display panel.

Programme and maintenance: with the weekly thermostat programme you can enable early start (Outputs → Thermostat): heating starts up to 2 hours earlier so that it is warm at the set time, and it learns the heating rate by itself. With the Heat Triac module you can enable valve exercising: once a week it opens the valve of a zone that has not heated for a week for 5 minutes. Both are off from the factory. The heating module never cools.

For each zone the web interface and Home Assistant show the floor temperature, the valve state and the reason (demand, idle, frost protection, sensor fault, overheating, floor limit). The decision logic is verified by an automated test on a PC, not on the board.

We will verify the sensor accuracy with specific actuators on the first piece.

8Troubleshooting

SymptomCauseRemedy
the zone does not heat, status “sensor fault” (E24)sensor not connected, short circuit, a different type or invalid sensor valuescheck the wiring (the web interface shows the resistance) and the sensor type in the web interface
the zone does not heat, status “floor limit”the floor is warmer than the limitwait, or adjust the limit according to the floor manufacturer
the actuator behaves the other way rounda different actuator type is set (NC / NO)correct the actuator type in the web interface

Special states of the switch

StateMeaningWhat to do
“Outputs are off” (E02)the selected module does not match the connected one, the module has no supply, or it is detected but not supported by this firmwarecorrect the selection on the Hardware page; for a module in development wait for firmware with support
“module: none” in the web interfaceno module selectedHardware → select the module, or the wizard
LEDs flashing bluesetup mode (5 min)connect to the SmartButton-XXXX Wi-Fi
the LED under the first area “breathes” whitea new switch offers touch calibration (2 min after power-up)hold this area for 3 s, or leave it
three red LED flashesa fault of severity “error” has occurredopen the web interface, the banner at the top shows the code
one area flashes red (E25)the switch has turned this area off because it would switch by itself (water on the glass, missing calibration)wipe the glass and wait half a minute; then calibrate the touch
only web interface and updates (E01)safe mode after 3 crashes within 60 s of startupload another firmware version, send the service bundle to the manufacturer
no network (E11)Wi-Fi or router outagetouch keeps controlling the outputs; without Ethernet the setup Wi-Fi starts after 3 min

9Error codes

From firmware 2.22.0 the switch reports faults and states as codes E01–E26. It evaluates the state every 2 s, for the first time 8 s after start. An error is reported when it lasts 2–4 s and disappears by itself as soon as it no longer applies. Severity: error = something does not work or is switched off for safety reasons, warning = works with limitations, information = for your information only. The codes only report; the protections of the modules work independently of them.

Where you see the errorHow
web interfacea banner at the top of every page: code, name and what to do
Home Assistantentity Fault (problem yes / no) and Errors (list of codes, “OK” without errors)
MQTTtopic <prefix>/<id>/faults (codes and English text, “OK” without errors)
Modbus TCP / RTUinput registers IR 46 (E01–E16) and IR 47 (E17–E32), bit n − 1 = code En, 0 = no error
event log and loga record when each code appears and disappears
LEDs on the panelwhen an error occurs they flash red three times; warnings and information do not flash
CodeSeverityMeaningTypical causeWhat to do
E01errorSafe modethe firmware crashed three times in a row within 60 s of startOutputs and integrations are off; the network, web interface and updates run. Upload another firmware version, send the service bundle.
E02errorPower module does not match the selectiona different module selected than connected; module without supply; detected but unsupported moduleThe outputs did not start. Correct the selection on the Hardware page.
E07warningThe BME688 sensor stopped respondingloose flat cable to the panel, faulty sensor. A sensor that is not fitted is not an error.Check the flat cable. An enabled thermostat keeps its output off meanwhile (E09).
E08warningTemperature source not available (panel without sensor; 5 min after start at the earliest)the source switch is off or has a different link key, Home Assistant has not sent the temperature for more than 5 minCheck the source switch or the automation in HA, or select another source (Panel & LED).
E09errorThe thermostat has no temperature (60 s after start at the earliest)a consequence of E07 or E08, or a thermostat without a sensor and without a temperature sourceThe thermostat output is off until the temperature is restored. Remove the cause.
E10warningMQTT not connected (for more than 2 min)wrong broker address or password, broker not running, network outageCheck the Integrations page and the broker. Local control keeps working.
E11warningNo network (for more than 2 min)cable unplugged, wrong Wi-Fi password, router switched offCheck the cable / Wi-Fi. Local control keeps working.
E12informationTime is not set (5 min after start)no access to NTP and after a power failureLog in to the web interface (the time is taken from the browser), or enable NTP.
E13warningLow free memorymany functions running at once (HTTPS, voice)Switch off unused functions or restart. If it keeps coming back, send the service package.
E14warningHigh temperature of the control board (default threshold 85 °C)poorly ventilated wall box, high load, high LED brightnessCheck ventilation and load. The threshold is in Diagnostics.
E15warningErrors on the panel busflat cable, connector, interferenceCheck the flat cable to the front panel.
E17warningHardware check warninge.g. the display touch controller was not foundFollow the text of the warning in the web interface.
E18informationThe last restart was a crash or a supply voltage dropfirmware fault, weak power supplyIf it happens once, nothing; the message disappears by itself an hour after start. If it repeats, send the service package.
E19warningTouch has drifted out of tunecover changed, humidity, dirt on the glassOnly a warning; touch keeps working. Wipe the glass and run the touch calibration.
E22warningAutomatic update failed, the version is being skippedthe new version was not confirmed after installation, or it could not be downloaded or verified 5 timesThe previous version is running. Install manually, or wait for a newer version.
E24errorFloor sensor fault or invalid sensor settingssensor open or shorted, converter does not respond, sensor type or values out of rangeThe zone does not heat, not even frost protection through this sensor. Check the sensor and the wires (the web interface shows the resistance), the sensor type and values.
E25errorThe touch area is switched offuncalibrated panel, water on the glass, a hand on the panel at power-on, interference, a faulty areaOnly the touch of this area is switched off (for the slider, the whole slider); its LED flashes red. The other areas, the web interface, Home Assistant and the scheduler keep working. Wipe the glass and wait about half a minute; if the error does not disappear, run the touch calibration in the web interface or with a short press of BOOT.

The table lists the codes that concern this module and the switch as a whole. The full list is in the manual for the board BALANS CORE.

10Declaration of conformity, disposal, manufacturer

EU declaration of conformity: in preparation. We will publish the document on this page once testing is finished (safety, EMC, radio, cybersecurity to EN 18031). Until the declaration of conformity is issued, the module is not intended for sale.

The switch contains a 2.4 GHz Wi-Fi radio (band 2400–2483.5 MHz). We will add the maximum transmit power and the simplified declaration of conformity after the conformity assessment.

Disposal (WEEE): do not dispose of the product with household waste (crossed-out wheelie bin symbol). Take it to a collection point for electrical equipment or return it to the seller.

Manufacturer: Ing. Tomáš Benešl – Benešl Automation, Ludvíka Svobody 12, 747 57 Slavkov, IČO 04250435, benesl@benesl-automation.cz, +420 732 413 773.

Downloads

Document version

VersionDateChange
1.3 (draft)13. 11. 2026firmware 2.38.3: switching off a faulty or wet area (E25), slider and level bar, double and triple touch, automatic module selection, Device health, password at handover and factory reset, heating: early start; renders with the corrected marking; board rev A0
1.2 (draft)12. 11. 2026firmware 2.36.11: handover to the customer, settings change history, lowest-brightness wizard, Show code button, plain Wi-Fi messages
1.1 (draft)11. 11. 2026firmware 2.35.0: setup wizard, touch calibration, error codes E01–E24, new mounting order and 3 × 6 screws, final renders
1.0 (draft)9. 11. 2026first issue, firmware 2.10.2