Request a quote
Benešl Automation / References / Development test lab
Case study · BAVIS · Research and testing

A test chamber for air pressure gust tests running on BAVIS

The development test lab of a building materials manufacturer in Brno tests building products such as windows in a chamber where fans and dampers create pressure gusts. BAVIS now handles chamber operation, fast data logging, test evaluation and the test report – from a browser on a PC, tablet or phone.

fast data samples
every 10 ms
analogue channels
10
chamber PLC
S7-1200
soak test
48 h

Starting point

The test is controlled by a Siemens S7-1200 PLC with a proven program, and operators used to run the chamber from the original panel HMI. The lab needed more: record the fast pressure curve without losing a single sample, evaluate every gust and issue a report for the client. All without touching the test logic in the PLC.

What we delivered

  • BAVIS with a chamber configuration replaced the original HMI. The test logic stayed in the PLC; the application controls and reads it.
  • Fast data without losses: the PLC fills a double buffer with 10 ms samples from ten analogue inputs and BAVIS reads it with a handshake, so no sample is lost. Live values refresh five times per second.
  • The PLC changes only added an interface for the web and the buffer. We made them directly in the original TIA Portal V17 project, so the customer did not have to upgrade.
  • Gust evaluation straight from the 10 ms data with tolerances set by the administrator, and a PDF test report with order details, charts, photos and signatures. Export to XLSX and CSV.
  • Pressure and strain gauge measurement from an NI card and pressure transducers in the same application, with sensor calibration and tare history.
  • Viewer, operator and administrator roles. Commands require permission, parameters are locked during a test and sensitive changes are protected by an electronic signature and an audit trail entry.
  • Bug reports straight from the application with a screenshot and diagnostics. When the lab has no internet, the report is saved as a ZIP.

How we verified it

  • A simulator of the chamber PLC: we tested the whole application without the chamber, in virtual commissioning.
  • Soak test: a 48-hour test with about 5,000 gusts in accelerated time, including connection dropouts.
  • PLC service settings are checked against the real PLC read-only before any change – nothing is written to the PLC.
  • Before each release we install the update over an older version on an isolated test Windows and check that data and settings are kept.

What this means for you

  • A proven PLC program does not need rewriting. A new HMI and data logging connect to it with minimal changes.
  • Fast data belongs in a buffer in the PLC, not in ordinary polling through the HMI. Only then is no sample lost.
  • What used to be hard-coded is now set by the administrator: screens, alarms, texts, report fields and sections.
  • Features created for this lab – NI cards, test reports, calibration and audit trail – are now part of the BAVIS core for other projects.

Planning a test bench or measurement?

Explore the anonymised test lab demo in your browser. Or send us a tag export from TIA Portal or a CSV and we will show you BAVIS on your own data.